Car Stackers

4.25 Car Stacking/Lift Systems Reference: 2016 NFPA 13 Section 5.4.2, A5.4.2(9), & 11.1.2(1); 2019 San Francisco Fire Code, Sections 105.7.26, 903.3.1.1 & 903.3.5. Purpose: Provide additional SFFD guidelines for sprinkler protection of car stackers not specifically addressed in 2016 NFPA 13.The sprinkler design criteria for car stackers/lift systems must extend 15 feet into adjacent areas that do not contain car stackers/lift systems. Parking garage areas containing Car Stackers / lift systems with a single lift platform shall be protected by an automatic wet-pipe sprinkler system designed to Extra Hazard (Group